Wire gauge question

  1. #1
    jeffrey776 jeffrey776 is offline

    Wire gauge question

    Hey guys,
    I'm needing some info. 120 volt @ 14.3 amps what wire gauge should I use?
    Thanks

  2. #2
    Reloadron Reloadron is offline
    Personally I would run with AWG12 while AWG14 would likely be OK. Really depends on variables like the insulation type used, open air or tight space, length of the run from source to load and other things. For residential use general wiring with for example Romex cable, I would still opt for AWG12.

    On another note I don't see 120 VAC as high voltage.

    Ron
    0
    Last edited by Reloadron; 3rd September 2011 at 11:31 PM.

  3. #3
    jpanhalt jpanhalt is offline
    What is the current rating of your circuit breaker? If 20A, then use 12 AWG.

    John
    0

  4. #4
    Reloadron Reloadron is offline
    Quote Originally Posted by jpanhalt View Post
    What is the current rating of your circuit breaker? If 20A, then use 12 AWG.

    John
    My bad, I should have mentioned that also.

    Ron
    0

  5. #5
    squishy36 squishy36 is offline
    Also pay attention to the length of run -- and bump up the wire diameter for long runs. I ran into this problem powering my ditch pump. My home's power comes from a power pole a couple hundred feet from my house. Then a wire from the house goes out to an outbuilding next to that power pole. I ran 12 gauge Romex for my 1 HP pump from the outbuilding to the pump with about another 100 feet of wire. I've measured about an 8% voltage drop from ideal and, when I had a borderline pump (bearings going out & finally died), I stuck a Variac on the circuit and bumped things up about 10 volts. Knowing what I know now, I would have used larger diameter wires, as amortized over the 25 years I've been using the setup, the incremental cost would have been negligible.
    0

  6. Thread Starter #6
    jeffrey776 jeffrey776 is offline
    Hey Guys thanks for the input. I rewiring a popcorn kettle the run is about 20" to the receptacle which plug and recep are rated at 30amp the breaker at the panel is 20amp and I'm using insulated heat resistant 12awg stranded wire. The reason I asked is that I had a total thermal meltdown in kettle compartment. I think perhaps the crimp terminals and wire lugs I was using may have damaged the wires or created hot spots where the two were joined, kind of like a kink in a hose situation?
    Soooo, can you recommend a brand of terminal or type of crimper designed for this type of application? I was thinking maybe I should use my Molex crimper next time it seems to be more subtle than the sheer squeezing force of my Klein wire crimpers.

    Again Thank You everyone for taking the time to read my post and help me in a most perplexing situation.
    0
    Last edited by jeffrey776; 5th September 2011 at 11:11 PM.

  7. #7
    jpanhalt jpanhalt is offline
    Quote Originally Posted by jeffrey776 View Post
    Hey Guys thanks for the input. I rewiring a popcorn kettle the run is about 20" to the receptacle which plug and recep are rated at 30amp the breaker at the panel is 20amp and I'm using insulated heat resistant 12awg stranded wire. The reason I asked is that I had a total thermal meltdown in kettle compartment. I think perhaps the crimp terminals and wire lugs I was using may have damaged the wires or created hot spots where the two were joined, kind of like a kink in a hose situation?
    Soooo, can you recommend a brand of terminal or type of crimper designed for this type of application? I was thinking maybe I should use my Molex crimper next time it seems to be more subtle than the sheer squeezing force of my Klein wire crimpers.

    Again Thank You everyone for taking the time to read my post and help me in a most perplexing situation.
    20A is 12 gauge. Most electrticians will tell you that, unless the distance is really large (one-way >100ft). 30A is 10 gauge. Be sure it's copper to copper. 12 AWG is usually solid; 10 AWG can be either solid or stranded -- I use stranded. Some people use stranded 12 AWG, because it pulls easier. It works, but most electricians I have talked to use solid.

    If you are getting meltdowns at 15A with 12 AWG, your connections are poor. Without a lot more detail it is impossible to give more specific advice.

    John
    0

  8. #8
    Reloadron Reloadron is offline
    Yeah, been there and seen that with heating elements. The connection to the heating element(s) should be made with a high temperature crimp lug. I don't know your location but if you are familiar with McMaster Carr Supply their part number 69405K93 would be for #8 lugs and for AWG 10-12 wire. You also want high temp wire to the actual heaters. Be aware these terminals are hard to crimp, hope you have strong hands. . I see you say:

    I'm using insulated heat resistant 12awg stranded wire.
    I don't know what heat resistant is degrees F but if you want some high temp wire designed for these applications I'll be happy to send you some. Do not use everyday terminal lugs or in a week you will be doing this again.

    Ron
    0

Tags
Similar Threads
Thread Starter Forum Replies Last Post
Wire gauge for 12v DC fan Rockyd General Electronics Chat 1 23rd August 2010, 04:36 AM
wire gauge with a small duty cycle justinlw General Electronics Chat 11 5th January 2007, 03:48 PM
Determining Wire Gauge justinlw General Electronics Chat 4 10th October 2006, 10:44 PM
Headphone wire (a question) SoftICE General Electronics Chat 2 10th February 2006, 01:58 PM
Wire Gauge and Current bryan Electronic Projects Design/Ideas/Reviews 19 25th October 2004, 05:37 AM
Electronic Circuits  |  Learning Electronics

Join our community with over 100,000 Members! It's free, easy and when you're logged in you have many more features! Click to register.
Page Time: 0.09182 seconds      Memory: 7,532 KB      Queries: 17      Templates: 0